Send us a quick message!
Call for guaranteed low pricing and quantity discounts!
Prime Rating: 68 kW (85 kVA)
Standby Rating: 75 kW (94 kVA)
60 Hertz

| Performance Data | ||
| Prime Rating | 68 kW | 85 kVA |
| Standby Rating | 75 kW | 94 kVA |
| Generator RPM | 1800 | |
| Voltage - Three Phase | 208, 220, 240, 416, 440, 460, 480V Switchable | |
| Voltage - Single Phase | 120, 127, 139, 240, 254, 277V Switchable | |
| Generator Design | Revolving field, Self-ventilated, Drip-proof, Single bearing | |
| Voltage Regulation (No Load to Full Load) | ±0.5 % | |
| Power Factor | 0.8 | |
| Armature Connection | Star with Neutral/ Zig Zag | |
| Excitation | Brushless with AVR | |
| No. Poles | 4-pole | |
| Frequency | 60 Hz | |
| Frequency Regulation (steady state load) | ±0.25 % | |
| Sound Level (Full Load at 23 ft.) | 63 dB(A) | |
![]()

![]()
Standard Features:
![]()
Optional Generator Features:
![]()
Optional Control Features:
![]()
Ultra-Silent Features:
![]()
| Generator Specifications | ||
| Design | Revolving field, self-ventilated, drip-proof, single bearing | |
| Armature Connection | Star w/ Neutral | Zig Zag |
| Phase | 3 | Single |
| Standby Output | 75 KW (94 KVA) | 66 KW |
| Prime Output | 68 KW (85 KVA) | 60 KW |
| 3Ø Voltage Voltage Selector Switch at 3Ø 240/139 | 208Y/120, 220Y/127, 240Y/139 | N/A |
| 3Ø Voltage Voltage Selector Switch at 3Ø 480/277 | 416Y/240, 440Y/254, 480Y/277 |
N/A |
| 1Ø Voltage Voltage Selector Switch at 1Ø 240/120 | N/A | 240/120 |
| Power Factor | 0.8 | 1.0 |
| Voltage Regulation | ±0.5% | |
| Generator RPM | 1800 | |
| Frequency | 60 Hz | |
| No. of Poles | 4 | |
| Excitation | Brushless with AVR | |
Frequency Regulation: No load to full load |
3~5% under varying loads from no load to 100% rated load |
|
Frequency Regulation: Steady State |
±0.5% of mean value for constant loads from no load to full load. |
|
| Insulation | Class F | |
| Sound Level dB(A) | 63 | |
| Engine Specifications | |
| Make | John Deere |
| Model | 4045HF285 |
| Emissions | EPA Tier 3 Certified |
| Starting system | Electric |
| Design | 4-cycle, water cooled, Direct injection, Turbocharged, air-to-air intercooled |
| Displacement | 4,500cc |
| No. cylinders | 4 |
| Bore | 106 mm |
| Stroke | 127 mm |
| Gross Engine Power Output | 126 hp (93.9kW) |
| BMEP | 230 psi (1589 kPa) |
| Piston Speed | 1500 ft./min. |
| Compression Ratio | 19:1 |
| Engine Speed | 1800 rpm |
| Overspeed Limit | 2100 rpm |
| Oil Capacity | 3.49 gal (13.2 L) |
| Battery | 12V 72Ah x 1 |
| Fuel System | |
| Fuel Tank Capacity | 40 gal (150.0 L) |
| Diesel Fuel at % of Load | gal/hr (L/hr) |
| 100% | 5.3 (20.1) |
| 75% | 4.3 (16.2) |
| 50% | 3.1 (11.9) |
| 25% | 2.0 (7.6) |
| Amperage | |
| Rated Voltage | Max Amps |
| 1Ø 120V | 188.9 (4 wire) |
| 1Ø 240V | 94.9 (4 wire) |
| 3Ø 240V | 204 Amps |
| 3Ø 480V | 102 Amps |
| Main Line Circuit Breaker Rating | 250 Amps |
| Over Current Releay Trip Set Point | 102 Amps |
![]()
John Deere Engine:
12 months from date of purchase and unlimited hours or 24 months
from date of purchase with 2000 hours (whichever ocurs first).
Generator:
24 months from date of purchase or 2000 hours (whichever occurs first).
Trailer:
12 months excluding normal wear items.
![]()
Generator is not intended for use in enclosed areas or where free flow of air is restricted.
Backfeed to a utility system can cause electrocution and/or property damage. Do not
connect to any building’s electrical system except through an approved device.
Specifications are subject to change without notice.
![]()
WhisperWatt DCA85USJ Spec Sheet